Electrical

Voltage Drop Calculator

Calculate voltage drop over a run and check it against the 3% guideline.

ft
Circular mils: 14 AWG=4110, 12=6530, 10=10380, 8=16510, 6=26240, 4=41740, 2=66360, 1/0=105600
12.9 for copper, 21.2 for aluminium.
Voltage drop
Volts dropped
Voltage at the load

These figures are for estimation only. All electrical work must be designed and verified by a licensed electrician and comply with the NEC and your local code.

How this calculator works

VD = 2 × K × amps × distance ÷ circular mils

The 2 accounts for current travelling out and back. For three-phase, replace it with 1.732. The NEC recommends keeping branch-circuit drop under 3% and total drop including the feeder under 5%.

Worked example

With load current 20 , one-way distance 100 ft, conductor size 6530 , system voltage 120 , conductor material k 12.9 , this calculator returns 6.58 .

Voltage drop by circuit length

Figures below assume load current 20 × conductor size 6530 × system voltage 120 × conductor material k 12.9 . Change any measurement in the calculator to get your own numbers.

One-way distanceVoltage dropVolts droppedVoltage at the load
25 ft1.651.98118.0
50 ft3.293.95116.0
75 ft4.945.93114.1
100 ft6.587.90112.1
150 ft9.8811.85108.1
200 ft13.1715.80104.2
300 ft19.7523.7196.29

A 20 A load on 12 AWG copper at 120 V. One-way distance — the formula already accounts for the return path.

Voltage drop on common circuits

JobSizeVoltage drop
Kitchen circuit, 14 AWG 15 × 50 ft × 4110 × 120 × 12.9 3.92
Bedroom circuit, 12 AWG 20 × 75 ft × 6530 × 120 × 12.9 4.94
Detached garage feeder 40 × 150 ft × 16510 × 240 × 12.9 3.91
Well pump, long run 10 × 300 ft × 10380 × 240 × 12.9 3.11
EV charger, 50 A 50 × 60 ft × 26240 × 240 × 12.9 1.23
Barn subpanel on aluminium 60 × 250 ft × 41740 × 240 × 21.2 6.35

Doubling the voltage quarters the percentage drop for the same power delivered, which is why long runs are almost always done at 240 V.

Wire size in circular mils

TypeCircular milsNotes
14 AWG4,110 15 A circuits
12 AWG6,530 20 A circuits
10 AWG10,380 30 A circuits
8 AWG16,510 40 A circuits
6 AWG26,240 55 A circuits
4 AWG41,740 70 A feeders
2 AWG66,360 95 A feeders
1/0 AWG105,600 125 A service

Use K = 12.9 for copper and 21.2 for aluminium. Going up one wire size increases circular mils by roughly 60%, which cuts the drop by about the same proportion.

Frequently asked questions

How do I calculate voltage drop?

Multiply 2 by K, by the current, by the one-way distance, then divide by the circular mils of the conductor. K is 12.9 for copper and 21.2 for aluminium.

How far can I run 12 gauge wire?

About 115 feet at 20 A on a 120 V circuit before drop reaches 3%. At 240 V the same conductor reaches roughly 230 feet, because the percentage drop halves.

What size wire do I need for a 100 foot run?

At 20 A and 120 V, 10 AWG copper keeps the drop under 3%; 12 AWG lands at about 3.9%. At 240 V, 12 AWG is comfortably within limits.

Is 3% voltage drop a code requirement?

No. NEC 210.19 and 215.2 recommend 3% on a branch circuit and 5% total including the feeder, but both appear in informational notes rather than enforceable text. Inspectors treat them as good practice.

What is an acceptable voltage drop?

The NEC recommends no more than 3% on a branch circuit and 5% total including the feeder. These are recommendations in informational notes rather than enforceable requirements, but equipment performance suffers beyond them.

How do I reduce voltage drop?

Increase the conductor size, shorten the run, or raise the system voltage. Going up one wire gauge reduces drop by roughly 20%; doubling the voltage cuts it by three quarters for the same power.

Why is the formula multiplied by 2?

Current travels the full length out to the load and back through the neutral, so the conductor length in the circuit is twice the one-way distance. Three-phase uses 1.732 instead because of the phase relationship.

Does voltage drop matter on short runs?

Rarely. Under about 50 ft on a standard branch circuit the drop is negligible. It becomes the governing factor on long runs to outbuildings, well pumps and detached garages.