Electrical

Wire Size Calculator

Find the conductor size a run needs to stay within your voltage drop limit.

ft
3% is the NEC recommendation for a branch circuit.
12.9 for copper, 21.2 for aluminium.
Circular mils required
Allowable drop
Cross-sectional area

Conductor sizing must also satisfy NEC ampacity tables, temperature correction and conduit fill. This calculator addresses voltage drop only. Have all work verified by a licensed electrician.

How this calculator works

circular mils = 2 × K × amps × distance ÷ allowable voltage drop

Compare the result against standard sizes: 14 AWG=4110, 12=6530, 10=10380, 8=16510, 6=26240, 4=41740, 3=52620, 2=66360, 1=83690, 1/0=105600. Round up to the next size — never down.

Worked example

With load current 20 , one-way distance 150 ft, system voltage 120 , maximum voltage drop 3 , conductor material k 12.9 , this calculator returns 21500 .

Frequently asked questions

What wire size do I need for a 20 amp circuit?

Twelve AWG copper meets ampacity for 20 amps, but voltage drop governs on long runs. At 150 ft on 120 V you need 21,500 circular mils — that is 6 AWG, three sizes larger than ampacity alone would suggest.

Does ampacity or voltage drop determine wire size?

Whichever demands the larger conductor. Ampacity is the code requirement and sets the minimum; voltage drop is a performance recommendation that frequently governs on runs over 100 ft.

Can I use aluminium instead of copper?

Yes for feeders and service conductors, and it costs considerably less. Aluminium carries about 61% of copper conductivity, so you need roughly two sizes larger, plus antioxidant compound and rated terminations.

What size wire for a detached garage?

It depends entirely on the load and distance — this is exactly the case where voltage drop governs. A 60 amp subpanel 150 ft away typically needs 2 AWG copper or 1/0 aluminium, not the 6 AWG ampacity alone would allow.